Tabla III - Conductores de cobre
SECCI (mm2) |
DIAMET (m) |
PESO (Kg / m) |
VELOC. VIENTO (Km / h) |
ESFUER- VIENTO (Kg / m) |
CARGA ESP VERTICAL (Kg /m.mm2) |
CARGA ESP HORIZONT. (Kg / m.mm2) |
CARGA ESP TOTAL (Kg/m.mm2) |
16 (16,55) |
5,1 |
0,1622 |
50 120 125 130 |
0,055 0,318 0,346 0,374 |
92.10-4 " " " |
33.2.10-4 192.10-4 209.10-4 226.10-4 |
97,7.10-4 205.10-4 228.10-4 244.10-4 |
25 (26,16) |
6,3 |
0,2606 |
50 120 125 130 |
0,069 0,394 0,428 0,462 |
" " " " |
26,4.10-4 151.10-4 164.10-4 177.10-4 |
95,5.10-4 177.10-4 188.10-4 200.10-4 |
35 (35,15) |
7,5 |
0,3233 |
50 120 125 130 |
0,082 0,469 0,510 0,550 |
" " " " |
28,3.10-4 133,5.10-4 145,0.10-4 157,0.10-4 |
95,0.10-4 162,5.10-4 171,5.10-4 182,0.10-4 |
50 (50,12) |
9,0 |
0,4626 |
50 120 125 130 |
0,898 0,562 0,611 0,660 |
" " " " |
19,6.10-4 112,0.10-4 122,0.10-4 132,0.10-4 |
94,0.10-4 145,0.10-4 152,0.10-4 161,0.10-4 |
70 (70,88) |
11 |
0,6542 |
50 120 125 130 |
0,120 0,687 0,746 0,807 |
" " " " |
16,9.10-4 96,9.10-4 105,0.10-4 114,0.10-4 |
93,5.10-4 133,5.10-4 139,8.10-4 146,8.10-4 |
95 (95,23) |
12,75 |
0,879 |
50 120 125 130 |
0,127 0,720 0,792 0,856 |
" " " " |
13,4.10-4 76,5.10-4 83,1.10-4 89,8.10-4 |
93,0.10-4 119,5.10-4 124,0.10-4 138,5.10-4 |
120 (119) |
14,15 |
1,098 |
50 120 125 130 |
0,141 0,858 0,878 0,950 |
" " " " |
11,8.10-4 68,0.10-4 73,8.10-4 79,8.10-4 |
92,8.10-4 114,3.10-4 118,0.10-4 122,0.10-4 |
150 (158,8) |
16,1 |
1,393 |
50 120 125 130 |
0,146 0,637 0,910 0,985 |
" " " " |
9,7.10-4 55,6.10-4 60,4.10-4 65,3.10-4 |
92,6.10-4 107,5.10-4 118,0.10-4 112,0.10-4 |
150 (150,8) |
16,1 |
1,393 |
50 120 125 130 |
0,146 0,637 0,910 0,985 |
" " " " |
9,7.10-4 55,6.10-4 60,4.10-4 65,3.10-4 |
92,6.10-4 107,5.10-4 118,0.10-4 116,0.10-4 |
185 (185,4) |
17,85 |
1,713 |
50 120 125 130 50 * |
0,162 0,982 1,010 1,092 0,343 |
" " " " 137,3.10-4 |
8,7.10-4 50,0.10-4 54,3.10-4 58,8.10-4 13,8.10-4 |
92,5.10-4 104,3.10-4 107,0.10-4 109,1.10-4 130,0.10-4 |
240 (240,6) |
20,25 |
2,297 |
50 120 125 130 50 * |
0,183 1,053 1,144 1,240 0,364 |
92,0.10-4 " " " 129,0.10-4 |
7,36.10-4 42,4.10-4 46,0.10-4 49,8.10-4 14,63.10-4 |
92,3.10-4 101,0.10-4 103,0.10-4 104,5.10 130,0.10-4 |
* cargas para conductores con manguito de hielo (espesor 10 mm).
Tabla IV - Conductores de aluminio - acero
SECCI (mm2) |
DIAMET (m) |
PESO (Kg / m) |
VELOC. VIENTO (Km / h) |
ESFUER- VIENTO (Kg / m) |
CARGA ESP VERTICAL (Kg /m.mm2) |
CARGA ESP HORIZONT. (Kg / m.mm2) |
CARGA ESP TOTAL (Kg/m.mm2) |
|
50/8 |
56,31 |
9,6 |
0,195 |
50 120 125 130 |
0,1045 0,6 0,651 0,705 |
35,4.10-4 " " " |
18,4.10-4 106,10-4 115,10-4 125.10-4 |
40.10-4 112.10-4 120.10-4 130.10-4 |
70/12 |
77,8 |
11,6 |
0,274 |
50 120 125 130 |
0,1265 0,723 0,785 0,850 |
" " " " |
16,8.10-4 93,5.10-4 101.10-4 110.10-4 |
39.10-4 99,5.10-4 107.10-4 115.10-4 |
95/15 |
105 |
13,4 |
0,368 |
50 120 125 130 |
0,134 0,77 0,835 0,905 |
" " " " |
12,7.10-4 73,5.10-4 79,5.10-4 86.10-4 |
37.10-4 81,5.10-4 86,5.10-4 93.10-4 |
120/21 |
143,5 |
15,7 |
0,50 |
50 120 125 130 |
0,157 0,905 0,98 1,058 |
" " " " |
10,9.10-4 63.10-4 68,3.10-4 73,8.10-4 |
37.10-4 72.10-4 77.10-4 81,5.10-4 |
150/25 |
174,3 |
17,3 |
0,61 |
50 120 125 130 |
0,156 0,9 0,98 1,06 |
" " " " |
8,95.10-4 51,5.10-4 56,9.10-4 60,9.10-4 |
36,6.10-4 63.10-4 66,5.10-4 70,5.10-4 |
185/32 |
215,5 |
19,2 |
0,76 |
50 120 125 130 50 * |
0,174 1,00 1,085 1,17 0,356 |
" " " " 75,6.10-4 |
8,1.10-4 46,3.10-4 50,03.10-4 54,5.10-4 16,5.10-4 |
36,3.10-4 58,47.10-4 61,7.10-4 65,10-4 77,5.10-4 |
240/40 |
276,1 |
21,7 |
0,97 |
50 120 125 130 50 * |
0,197 1,125 1,22 1,32 0,378 |
35,4.10-4 " " " 69,5.10-4 |
7,1.10-4 40,9.10-4 44,2.10-4 47,8.10-4 14,5.10-4 |
36,2.10-4 54,10-4 56,8.10-4 59,5.10-4 10.10-4 |
300/50 |
344,4 |
24,2 |
1,21 |
50 120 125 130 50 * |
0,22 1,25 1,37 1,48 0,4 |
35,4.10-4 " " " 64,6.10-4 |
6,4.10-4 36,5.10-4 39,6.10-4 43.10-4 11,6.10-4 |
36.10-4 50,9.10-4 53.10-4 55,5.10-4 64,9.10-4 |
* cargas para conductores con manguito de hielo (espesor 10 mm).
Tabla V - Conductores de aleación de aluminio
SECCI (mm2) |
DIAMET (m) |
PESO (Kg / m) |
VELOC. VIENTO (Km / h) |
ESFUER- VIENTO (Kg / m) |
CARGA ESP VERTICAL (Kg /m.mm2) |
CARGA ESP HORIZONT. (Kg / m.mm2) |
CARGA ESP TOTAL (Kg/m.mm2) |
50 |
9 |
0,1363 |
50 120 125 130 |
0,898 0,561 0,611 0,661 |
27,6.10-4 " " " |
19,6.10-4 112.10-4 122.10-4 132.10-4 |
34.10-4 116,5.10-4 125.10-4 134,9.10-4 |
95 |
12,75 |
0,268 |
50 120 125 130 |
0,1275 0,729 0,791 0,856 |
" " " " |
13,4.10-4 16,5.10-4 83,3.10-4 90.10-4 |
30,7.10-4 31,3.10-4 87,8.10-4 94.10-4 |
160 |
16,1 |
0,4267 |
50 120 125 130 |
0,146 0,386 0,94 0,985 |
" " " " |
9,7.10-4 56,8.10-4 60,7.10-4 65,7.10-4 |
29,2.10-4 62,2.10-4 66,7.10-4 71,1.10-4 |
185 |
17,85 |
0,5245 |
50 120 125 130 50 * |
0,161 0,93 1,01 1,09 0,343 |
" " " " 73,3.10 |
8,7.10-4 50,3.10-4 54,6.10-4 59.10-4 18,55.10-4 |
28,9.10-4 67,4.10-4 61,1.10-4 65.10-4 75,6.10-4 |
240 |
19,95 |
0,6551 |
50 120 125 130 50 * |
0,181 1,037 1,127 1,22 0,362 |
27,6.10-4 " " " 64,6.10-4 |
7,55.10-4 43,2.10-4 46,9.10-4 50,8.10-4 15,1.10-4 |
28,6.10-4 51,3.10-4 54,3.10-4 57,8.10-4 66,4.10-4 |
300 |
22,95 |
8,868 |
50 120 125 130 50 * |
0,298 1,195 1,298 1,465 0,39 |
27,6.10-4 " " " 61,7.10-4 |
6,94.10-4 39,8.10-4 43,2.10-4 46,7.10-4 13.10-4 |
28,4.10-4 48,4.10-4 51,2.10-4 54,2.10-4 63.10-4 |
400 |
25,65 |
1,084 |
50 120 125 130 50 * |
0,233 1,338 1,48 1,57 0,415 |
27,6.10-4 " " " 53,8.10-4 |
5,82.10-4 33,4.10-4 36,2.10-4 39,2.10-4 10,4.10-4 |
28,2.10-4 43,3.10-4 45,6.10-4 48.10-4 54,8.10-4 |
* cargas para conductores con manguito de hielo (espesor 10 mm).